LPA® 875-SS-080-STD-B

Product Highlight

The Thermodynamic Principles of LPA

Most current refrigeration and air conditioning systems waste 20% to 40% of

Co2 Liquid Refrigerant Pump & LPA Economizer

The LPA® pump is an open-drive sealed unit with important design features:

DXFC™ Wall Mounted Split AC unit with Outdoor Condenser

[Public Disclosure-23rd October 2016] DXFC, DX free cooling the alternative to running

LPA® 875-SS-080-STD-B

875-SS-080-STD-B

875-SS-080-STD-B | 4 to 45 GPM | Head 50 feet

The model 875-SS-080-STD-B is currently in production having K65 tube connections rated at 80 bar.

  • PS 1,160 psi / 80 bar
  • PT 1,659 psi / 115 bar
  • TS Min -30°F / -29°C
  • TS Max 160°F / +72°C
  • Inlet K65 Tube 1-5/8″
  • Outlet K65 Tube 1-1/8″”
  • Motor Power .6hp / 60Hz
  • Voltage 208-230 /460
  • Ampere 2.2-2 / 1
  • Phase 3PH
  • Frequency 50 / 60Hz
  • Thermal Overload

Leave a Reply



NEED HELP? Click here for online help